STR.C1 - Concrete Moment Frame

The following models are available:

STR.C1.H.HC | Structural, Reinforced Concrete Moment Resisting Frames, High-Rise, High-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
High-Rise Building with more than 8 stories.
Design Level Approximate Basis:
Post-1975 construction in UBC Seismic Zone 4, NEHRP Map Area 7.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.H.LC | Structural, Reinforced Concrete Moment Resisting Frames, High-Rise, Low-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
High-Rise Building with more than 8 stories.
Design Level Approximate Basis:
1941-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5
Post-1941 construction in UBC Seismic Zone 2A, NEHRP Map Area 4
Post-1975 construction in UBC Seismic Zone 1, NEHRP Map Area 2/3

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.H.MC | Structural, Reinforced Concrete Moment Resisting Frames, High-Rise, Moderate-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
High-Rise Building with more than 8 stories.
Design Level Approximate Basis:
Post-1941 construction in UBC Seismic Zone 3, NEHRP Map Area 6
Post-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.H.PC | Structural, Reinforced Concrete Moment Resisting Frames, High-Rise, Pre-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
High-Rise Building with more than 8 stories.
Design Level: Approximate Basis: UBC Seismic Zone 0, NEHRP Map Area 1.
Pre-1941 construction in all other UBC and NEHRP areas.
Pre-Code damage functions are appropriate for modeling older buildings that were not designed for earthquake load, regardless of where they are located in the United States.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.L.HC | Structural, Reinforced Concrete Moment Resisting Frames, Low-Rise, High-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Low-Rise Building with 1-3 stories.
Design Level Approximate Basis:
Post-1975 construction in UBC Seismic Zone 4, NEHRP Map Area 7.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.L.LC | Structural, Reinforced Concrete Moment Resisting Frames, Low-Rise, Low-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Low-Rise Building with 1-3 stories.
Design Level Approximate Basis:
1941-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5
Post-1941 construction in UBC Seismic Zone 2A, NEHRP Map Area 4
Post-1975 construction in UBC Seismic Zone 1, NEHRP Map Area 2/3

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.L.MC | Structural, Reinforced Concrete Moment Resisting Frames, Low-Rise, Moderate-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Low-Rise Building with 1-3 stories.
Design Level Approximate Basis:
Post-1941 construction in UBC Seismic Zone 3, NEHRP Map Area 6
Post-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.L.PC | Structural, Reinforced Concrete Moment Resisting Frames, Low-Rise, Pre-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Low-Rise Building with 1-3 stories.
Design Level: Approximate Basis: UBC Seismic Zone 0, NEHRP Map Area 1.
Pre-1941 construction in all other UBC and NEHRP areas.
Pre-Code damage functions are appropriate for modeling older buildings that were not designed for earthquake load, regardless of where they are located in the United States.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.M.HC | Structural, Reinforced Concrete Moment Resisting Frames, Mid-Rise, High-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Mid-Rise Building with 4-7 stories.
Design Level Approximate Basis:
Post-1975 construction in UBC Seismic Zone 4, NEHRP Map Area 7.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.M.LC | Structural, Reinforced Concrete Moment Resisting Frames, Mid-Rise, Low-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Mid-Rise Building with 4-7 stories.
Design Level Approximate Basis:
1941-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5
Post-1941 construction in UBC Seismic Zone 2A, NEHRP Map Area 4
Post-1975 construction in UBC Seismic Zone 1, NEHRP Map Area 2/3

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.M.MC | Structural, Reinforced Concrete Moment Resisting Frames, Mid-Rise, Moderate-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Mid-Rise Building with 4-7 stories.
Design Level Approximate Basis:
Post-1941 construction in UBC Seismic Zone 3, NEHRP Map Area 6
Post-1975 construction in UBC Seismic Zone 2B, NEHRP Map Area 5.

Suggested Block Size: 1 EA (round up to integer quantity)


STR.C1.M.PC | Structural, Reinforced Concrete Moment Resisting Frames, Mid-Rise, Pre-Code

Structural components represent the structural system in the building.
Structural System: These buildings are similar to steel moment frame buildings except that the frames are reinforced concrete. There are a large variety of frame systems. Some older concrete frames may be proportioned and detailed such that brittle failure of the frame members can occur in earthquakes, leading to partial or full collapse of the buildings. Modern frames in zones of high seismicity are proportioned and detailed for ductile behavior and are likely to undergo large deformations during an earthquake without brittle failure of frame members or collapse.
Mid-Rise Building with 4-7 stories.
Design Level: Approximate Basis: UBC Seismic Zone 0, NEHRP Map Area 1.
Pre-1941 construction in all other UBC and NEHRP areas.
Pre-Code damage functions are appropriate for modeling older buildings that were not designed for earthquake load, regardless of where they are located in the United States.

Suggested Block Size: 1 EA (round up to integer quantity)